Notifier Fire Alarms – NFS2-640

Beautifully suited for all your web-based needs

Notifier Fire Alarms – NFS2-640

In stock N/A .

The NFS2-640 intelligent Fire Alarm Control Panel is part of the ONYX® Series of Fire Alarm Controls from NOTIFIER. In stand-alone or network configurations, ONYX Series products meet virtually every application requirement. The NFS2-640’s modular design makes system planning easier. The panel can be configured with just a few devices for small building applications, or networked with many devices to protect a large campus or a high-rise office block. Simply add additional peripheral equipment to suit the application. A host of other options are available, including single- or multichannel voice; firefighter’s telephone; LED, LCD, or PC-based graphic annunciators; networking; advanced detection products for challenging environments; wireless fire protection; and many additional options. NOTE: Unless called out with a version-specific “E” at the end of the part number, “NFS2-640” refers to models NFS2-640 and NFS2-640E; similarly, “CPU2-640” refers to models CPU2-640 and CPU2-640E.

Certified for seismic applications when used with the appropriate seismic mounting kit.
• Approved for Marine applications when used with listed compatible equipment. See DN-60688.
• One, expandable to two, isolated intelligent Signaling Line Circuit (SLC) Style 4, 6 or 7.
• Wireless fire protection using SWIFT Smart Wireless Integrated Fire Technology. See DN-60820.
• Up to 159 detectors and 159 modules per SLC; 318 devices per loop/636 per FACP or network node.
– Detectors can be any mix of ion, photo, thermal, or multisensor; wireless detectors are available for use with the FWSG.
– Modules include addressable pull stations, normally open contact devices, two-wire smoke detectors, notification, or relay; wireless modules are available for use with the FWSG.
• Standard 80-character display, 640-character large display (NCA-2), or display-less (a node on a network).
• Network options:
– High-speed network for up to 200 nodes (NFS2-3030, ONYXWorks, NFS-3030, NFS-640, and NCA).
– Standard network for up to 103 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-300/400, AFP-1010, and AM2020). Up to 54 nodes when DVC-EM is used in network paging.
• 6.0 A switch mode power supply with four Class A/B built-in Notification Appliance Circuits (NAC). Selectable System Sensor, Wheelock, or Gentex strobe synchronization.
• Built-in Alarm, Trouble, Security, and Supervisory relays.
• VeriFire® Tools online or offline programming utility. Upload/ Download, save, store, check, compare, and simulate panel databases. Upgrade panel firmware.
• Autoprogramming and Walk Test reports.

Specifications

Signaling Line Circuits (SLCs) 1 expandable to 2; Style 4, 6, or 7
Intelligent Devices 636 total devices; 159 detectors/159 modules per SLC
Notification Appliance Circuits (NACs) 4 (built in); 1.5 amps ea.
Voice Evacuation Available Yes: with integrated Digital Voice Command
Power 6 amps total system power
Annunciators
32 LCD type
32 ACS type
Networkable Yes: NOTI-FIRE-NET or High-Speed NOTI-FIRE-NET​
FOR CURRENT PRICING OR TO PLACE AN ORDER PLEASE CONTACT OUR KNOWLEDGEABLE AND PROFESSIONAL CUSTOMER SERVICE TEAM:
  • PHONE: 419-661-0678
  • EMAIL
CLICK TO SUBMIT AN ITEMIZED RFQ
Click for a Quick Quote

IF YOU CAN'T FIND WHAT YOU NEED OR REQUIRE A CUSTOM PART SIMPLY CALL AND SPEAK TO ONE OF OUR KNOWLEDGEABLE FLUID CONNECTION SPECIALISTS. THEY CAN WALK YOU THROUGH THEORDERING PROCESS QUICKLY AND PROFESSIONALLY.

Torrence Sound

Please submit your audio, video, security, and/or communication requirements and one of our specialists will contact you.

Contact Us
Contact Us